Practical experience of insulation condition evaluation in an on-site HV installation applying a PD measuring procedure

Álvarez Gómez, Fernando ORCID: https://orcid.org/0000-0002-1944-9823, Garnacho Vecino, Fernando ORCID: https://orcid.org/0000-0002-7752-8810, Albarracín Sánchez, Ricardo ORCID: https://orcid.org/0000-0003-1586-5931, Granizo Arrabé, Ricardo ORCID: https://orcid.org/0000-0001-5882-9311, Dong, Ming and Ortego la Moneda, Javier (2016). Practical experience of insulation condition evaluation in an on-site HV installation applying a PD measuring procedure. In: "International Conference on Condition Monitoring and Diagnosis 2016 (CMD 2016)", 25/09/2016-28/09/2016, Xi'an, China. ISBN 978-1-5090-3399-7 / 978-1-5090-3397-3. pp. 509-513. https://doi.org/10.1109/CMD.2016.7757874.

Description

Title: Practical experience of insulation condition evaluation in an on-site HV installation applying a PD measuring procedure
Author/s:
Item Type: Presentation at Congress or Conference (Article)
Event Title: International Conference on Condition Monitoring and Diagnosis 2016 (CMD 2016)
Event Dates: 25/09/2016-28/09/2016
Event Location: Xi'an, China
Title of Book: 2016 International Conference on Condition Monitoring and Diagnosis (CMD 2016)
Date: December 2016
ISBN: 978-1-5090-3399-7 / 978-1-5090-3397-3
Subjects:
Freetext Keywords: Insulation testing; Partial discharges; Partial discharge measurement; Dielectric breakdown; UHF measurements; Pattern recognition
Faculty: E.T.S.I. Diseño Industrial (UPM)
Department: Ingeniería Eléctrica, Electrónica Automática y Física Aplicada
Creative Commons Licenses: Recognition - No derivative works - Non commercial

Full text

[thumbnail of INVE_MEM_2016_266058.pdf]
Preview
PDF - Requires a PDF viewer, such as GSview, Xpdf or Adobe Acrobat Reader
Download (13MB) | Preview

Abstract

Analysis of the types of defects and the degradation modes in different insulation materials of highvoltage (HV) electrical systems has shown that the presence of partial discharges (PD) is a very common characteristic in all of them. Once PD activity is detected, the identification and localization of the associated type of defect is very important to evaluate whether the discharges are harmful or not. During the last two decades, different approaches have been developed and applied to PD measurement and processing techniques to deal with the most common problems arising in on-site and on-line measurements, such as: high levels of background noise, appearance of interferences, simultaneous presence of different PD sources and the difficulty of locating the site of the defects and to identify them. This paper proposes a measuring method together with the implementation of three signal processing tools in order to overcome all these difficulties that appear in on-site and on-line tests. The measuring method has been implemented to evaluate in an on-site practical experience the insulation condition of the power equipment in a GIS substation. After the application of the method, important insulation defects were detected, identified and localized, on time to avoid uncontrolled failures in the electrical system of the substation under test.

More information

Item ID: 48824
DC Identifier: https://oa.upm.es/48824/
OAI Identifier: oai:oa.upm.es:48824
DOI: 10.1109/CMD.2016.7757874
Official URL: http://ieeexplore.ieee.org/document/7757874/
Deposited by: Memoria Investigacion
Deposited on: 20 Dec 2017 12:21
Last Modified: 09 Oct 2020 06:04
  • Logo InvestigaM (UPM)
  • Logo GEOUP4
  • Logo Open Access
  • Open Access
  • Logo Sherpa/Romeo
    Check whether the anglo-saxon journal in which you have published an article allows you to also publish it under open access.
  • Logo Dulcinea
    Check whether the spanish journal in which you have published an article allows you to also publish it under open access.
  • Logo de Recolecta
  • Logo del Observatorio I+D+i UPM
  • Logo de OpenCourseWare UPM