Detection and localization of defects in cable sheath of cross-bonding configuration by sheath currents

Shokry Nada Faragalla, Marina Adel, Khamlichi, Abderrahim, Garnacho Vecino, Fernando, Martínez Malo, Julio and Álvarez Gómez, Fernando (2019). Detection and localization of defects in cable sheath of cross-bonding configuration by sheath currents. "IEEE Transactions on Power Delivery" ; pp. 1-11. ISSN 0885-8977. https://doi.org/10.1109/TPWRD.2019.2903329.

Description

Title: Detection and localization of defects in cable sheath of cross-bonding configuration by sheath currents
Author/s:
  • Shokry Nada Faragalla, Marina Adel
  • Khamlichi, Abderrahim
  • Garnacho Vecino, Fernando
  • Martínez Malo, Julio
  • Álvarez Gómez, Fernando
Item Type: Article
Título de Revista/Publicación: IEEE Transactions on Power Delivery
Date: 2019
ISSN: 0885-8977
Subjects:
Freetext Keywords: Condition monitoring; Current measurements; Electric breakdown; Cable shielding; Sheath current; Fault current
Faculty: E.T.S.I. Diseño Industrial (UPM)
Department: Ingeniería Eléctrica, Electrónica Automática y Física Aplicada
Creative Commons Licenses: Recognition - No derivative works - Non commercial

Full text

[thumbnail of INVE_MEM_2019_292718.pdf]
Preview
PDF - Requires a PDF viewer, such as GSview, Xpdf or Adobe Acrobat Reader
Download (14MB) | Preview

Abstract

Nowadays many researchers are focusing on on-line condition monitoring of high-voltage (HV) insulated cable systems to prevent failures. With the aim of reducing the voltage induced in the cable sheaths, cross-bonding (CB) grounding cable systems are used in long distance power transmission land lines. This paper proposes a new criterion for the detection and localization of defects that might occur in the cables sheath when a CB configuration is adopted. The criterion proposed can be applied at different levels of load current. For the application of the criterion, the cable system under evaluation is modeled using the ATP software. Various practical cases were studied showing the effectiveness of the criterion for the detection and localization of different types of defects in simulated cable systems. Furthermore, in order to validate the criteria adopted for the defect detection, based on the ATP model, a real defected case was evaluated. The results obtained proved that this criterion is suitable for the detection and localization of defects in the cables sheath, when on-line measurements are performed in monitoring applications.

Funding Projects

Type
Code
Acronym
Leader
Title
Horizon 2020
676042
MEAN4SG
Fundación CIRCE-Centro de Investigación de Recursos y Consumos Energéticos
Metrology Excellence Academic Network for Smart Grids

More information

Item ID: 54242
DC Identifier: https://oa.upm.es/54242/
OAI Identifier: oai:oa.upm.es:54242
DOI: 10.1109/TPWRD.2019.2903329
Official URL: https://ieeexplore.ieee.org/document/8661667
Deposited by: Memoria Investigacion
Deposited on: 14 Mar 2019 09:04
Last Modified: 31 Dec 2019 23:30
  • Logo InvestigaM (UPM)
  • Logo GEOUP4
  • Logo Open Access
  • Open Access
  • Logo Sherpa/Romeo
    Check whether the anglo-saxon journal in which you have published an article allows you to also publish it under open access.
  • Logo Dulcinea
    Check whether the spanish journal in which you have published an article allows you to also publish it under open access.
  • Logo de Recolecta
  • Logo del Observatorio I+D+i UPM
  • Logo de OpenCourseWare UPM