New Differential Protection for Variable Speed Doubly Fed Induction Machines

Zarei, Mohammad Ebrahim, Platero Gaona, Carlos Antonio ORCID: https://orcid.org/0000-0002-7007-2566, Veganzones Nicolas, Carlos ORCID: https://orcid.org/0000-0003-4015-3557 and Arribas, Jaime R. (2018). New Differential Protection for Variable Speed Doubly Fed Induction Machines. In: "2018 XIII International Conference on Electrical Machines (ICEM)", 03 - 06 September, 2018, Alexandroupoli, Greece. ISBN 978-1-5386-2477-7. pp. 1906-1911. https://doi.org/10.1109/ICELMACH.2018.8507073.

Description

Title: New Differential Protection for Variable Speed Doubly Fed Induction Machines
Author/s:
Item Type: Presentation at Congress or Conference (Article)
Event Title: 2018 XIII International Conference on Electrical Machines (ICEM)
Event Dates: 03 - 06 September, 2018
Event Location: Alexandroupoli, Greece
Title of Book: 2018 XIII International Conference on Electrical Machines (ICEM)
Date: 2018
ISBN: 978-1-5386-2477-7
Subjects:
Freetext Keywords: Variable speed Doubly Fed Induction machine (DFIM), Differential protection, Wind turbine generation, hydroelectric power generation.
Faculty: E.T.S.I. Industriales (UPM)
Department: Ingeniería Eléctrica, Electrónica Automática y Física Aplicada
Creative Commons Licenses: Recognition - No derivative works - Non commercial

Full text

[thumbnail of INVE_MEM_2018_298547.pdf]
Preview
PDF - Requires a PDF viewer, such as GSview, Xpdf or Adobe Acrobat Reader
Download (1MB) | Preview

Abstract

This paper presents a novel differential protection for the variable speed doubly fed induction machines (DFIMs), which typically are working as a generator in wind turbine systems and working as motor/generator in pump storage hydropower plants. The proposed protection, which is based on the comparison of the vector components Id-Iq of the rotor and stator currents, can protect the whole induction machine during the internal faults. This protection considers the dynamic variation of the rotor frequency and the extremely low rotor frequency along the different operation points of the DFIM. The proposed relay is validated in Matlab Simulink environment for a 2 MW DFIM, and the results show that the proposed differential protection protects effectively the entire induction machine during internal faults.

More information

Item ID: 55499
DC Identifier: https://oa.upm.es/55499/
OAI Identifier: oai:oa.upm.es:55499
DOI: 10.1109/ICELMACH.2018.8507073
Official URL: http://www.icem.cc/2018/
Deposited by: Memoria Investigacion
Deposited on: 21 Jun 2019 15:11
Last Modified: 21 Jun 2019 15:11
  • Logo InvestigaM (UPM)
  • Logo GEOUP4
  • Logo Open Access
  • Open Access
  • Logo Sherpa/Romeo
    Check whether the anglo-saxon journal in which you have published an article allows you to also publish it under open access.
  • Logo Dulcinea
    Check whether the spanish journal in which you have published an article allows you to also publish it under open access.
  • Logo de Recolecta
  • Logo del Observatorio I+D+i UPM
  • Logo de OpenCourseWare UPM