TY - CONF Y1 - 2013/// EP - 133 KW - Stator ground fault KW - fault location KW - generator protection. T2 - 12th International Conference on Environment and Electrical Engineering. EEEIC 2013 M2 - Wroclaw, Poland N2 - Locating stator-winding ground faults accurately is a very difficult task. In this paper the grounding circuit measurements are evaluated in order to obtain information about the stator ground-fault location in synchronous generators. In power generators grounded through a high impedance, the relation between the neutral voltage and the phase voltage provide a first estimation of the fault location. The location error by using this ratio depends on the fault resistance and the value of the capacitance to ground of the stator winding. However, the error added by ignoring the value of the fault resistance is the most relevant term. This location estimation and the location error have been evaluated through the data of a real synchronous machine. SN - 978-1-4799-2803-3 SP - 229 TI - Evaluation of the Grounding Circuit Measurements for Stator Ground-Fault Location of Synchronous Generators ID - upm29661 PB - IEEE UR - http://ieeexplore.ieee.org/xpl/articleDetails.jsp?arnumber=6737913&punumber%3D6731714%26filter%3DAND%28p_IS_Number%3A6737870%29%26pageNumber%3D2 AV - public A1 - Blánquez Delgado, Francisco A1 - Rebollo López, Emilio A1 - Platero Gaona, Carlos Antonio ER -