Battery energy storage system contribution to primary frequency control in isolated power systems.
"Access", v. 13
;
ISSN 2169-3536.
https://doi.org/10.1109/access.2025.3583228.
| Título: | Battery energy storage system contribution to primary frequency control in isolated power systems |
|---|---|
| Autor/es: |
|
| Tipo de Documento: | Artículo |
| Título de Revista/Publicación: | Access |
| Fecha: | 25 Junio 2025 |
| ISSN: | 2169-3536 |
| Volumen: | 13 |
| Materias: | |
| ODS: | |
| Palabras Clave Informales: | Battery energy storage system; hybrid isolated WDPS; primary frequency control; SPBA; renewable energy; droop control; frequency deviation |
| Escuela: | E.T.S.I. Caminos, Canales y Puertos (UPM) |
| Departamento: | Ingeniería Civil: Hidráulica, Energía y Medio Ambiente |
| Licencias Creative Commons: | Reconocimiento - Sin obra derivada - No comercial |
|
PDF (Portable Document Format)
- Se necesita un visor de ficheros PDF, como GSview, Xpdf o Adobe Acrobat Reader
Descargar (2MB) |
Increased renewable energy penetration into conventional power plants results in significant frequency regulation (FR) problems, particularly at island power systems. To overcome FR problems, an energy storage system plays an important role. Therefore, a battery energy storage system (BESS) is proposed to provide primary frequency control (PFC) for San Cristobal Island hybrid wind diesel power system (WDPS) in this paper. The aim of this paper is to highlight the improvements achieved using BESS and estimate the optimal size of that BESS for San Cristobal WDPS. Therefore, a permanent magnet synchronous generator (PMSG) based variable speed wind turbine (VSWT) with synthetic (droop) control is used, which enables VSWT to release inertia during contingencies. A novel controller tuning methodology, named student psychology-based algorithm (SPBA), is used to optimally tune the BESS with hybrid WDPS and to estimate BESS size. In addition, several configurations set such as BESS with VSWT and/or diesel power plant (DPP) or both, are presented in this paper to highlight the optimal tuning effects. Moreover, the BESS based WDPS is tested under various real-world scenarios such as loss of wind generator, steadily increase wind speed (1Vw ≈ 0.81 ms−1), variable wind speed, variable load demand (Pload) and simultaneously change in Vw and Pload. Finally, hybrid BESS based WDPS is tested in a real time environment (OPAL-RT) which validates its performance. Results show the significant reduction in frequency deviation, optimal sizing of BESS and optimal tuning of the whole WDPS.
| ID de Registro: | 90084 |
|---|---|
| Identificador DC: | https://oa.upm.es/90084/ |
| Identificador OAI: | oai:oa.upm.es:90084 |
| URL Portal Científico: | https://portalcientifico.upm.es/es/ipublic/item/10376289 |
| Identificador DOI: | 10.1109/access.2025.3583228 |
| Depositado por: | iMarina Portal Científico |
| Depositado el: | 04 Sep 2025 11:03 |
| Ultima Modificación: | 09 Sep 2025 10:55 |
Publicar en el Archivo Digital desde el Portal Científico