Is evaporative cooling an efficient solution for ensuring air quality and thermal comfort in overheated classrooms in a dry Mediterranean climate?

Aruta, Giuseppe, Escandón Ramírez, Rocío ORCID: https://orcid.org/0000-0003-0531-698X, Calama González, Carmen María ORCID: https://orcid.org/0000-0002-6511-2885, Ascione, Fabrizio ORCID: https://orcid.org/0009-0007-5631-2379 and Suárez Medina, Rafael ORCID: https://orcid.org/0000-0001-6136-1596 (2026). Is evaporative cooling an efficient solution for ensuring air quality and thermal comfort in overheated classrooms in a dry Mediterranean climate?. "Energy and Buildings" (n. 350); pp. 1-17. ISSN 0378-7788. https://doi.org/10.1016/j.enbuild.2025.116660.

Descripción

Título: Is evaporative cooling an efficient solution for ensuring air quality and thermal comfort in overheated classrooms in a dry Mediterranean climate?
Autor/es:
Tipo de Documento: Artículo
Título de Revista/Publicación: Energy and Buildings
Fecha: 1 Enero 2026
ISSN: 0378-7788
Número: 350
Materias:
ODS:
Palabras Clave Informales: Confort térmico ; Escuelas ; Clima mediterráneo ; Calidad del aire interior ; Sistemas de enfriamiento evaporativo ; Sur de España
Escuela: E.T.S. de Edificación (UPM)
Departamento: Construcciones Arquitectónicas y su Control
Licencias Creative Commons: Reconocimiento - Sin obra derivada - No comercial

Texto completo

[thumbnail of 10401753.pdf] PDF (Portable Document Format) - Se necesita un visor de ficheros PDF, como GSview, Xpdf o Adobe Acrobat Reader
Descargar (16MB)

Resumen

A large percentage of school buildings in Mediterranean climates that rely solely on natural ventilation face critical issues related to indoor overheating and poor air quality. Despite the severity of these challenges, there is limited research quantifying the problem and exploring viable cooling solutions that align with nearly zero-energy building (nZEB) standards. This study aims to fill that gap by presenting a case study on the environmental performance of a classroom with a direct evaporative cooling system. The school is located in southern Spain, a region characterised by a hot and dry Mediterranean climate. The primary objective is to assess whether such a system can ensure both thermal comfort and adequate indoor air quality during periods of overheating. Based on on-site monitoring data, an EnergyPlus simulation model was calibrated and validated. This model was then used to test a range of current and future climate conditions, as well as different ventilation strategies, including natural ventilation and evaporative cooling with different air change rates. The results demonstrate the effectiveness of the direct evaporative cooling system compared to conventional natural ventilation, reducing overheating hours by up to 26% and lowering indoor temperatures by as much as 6 °C.

Proyectos asociados

Tipo
Código
Acrónimo
Responsable
Título
Gobierno de España
PID2020-117722RB-I00
Sin especificar
Sin especificar
Sin especificar

Más información

ID de Registro: 91822
Identificador DC: https://oa.upm.es/91822/
Identificador OAI: oai:oa.upm.es:91822
URL Portal Científico: https://portalcientifico.upm.es/es/ipublic/item/10401753
Identificador DOI: 10.1016/j.enbuild.2025.116660
URL Oficial: https://www.sciencedirect.com/science/article/pii/...
Depositado por: iMarina Portal Científico
Depositado el: 12 Nov 2025 07:06
Ultima Modificación: 12 Nov 2025 07:22