Carbon footprint (Scope 2) and energy intensity per activity in intermediate-complexity hospitals in the Community of Madrid : panel analysis (2016-2024)

Campos Vásquez, David ORCID: https://orcid.org/0009-0000-0297-1474, Río Merino, Mercedes del ORCID: https://orcid.org/0000-0002-4106-4233 and Villoria Sáez, Paola ORCID: https://orcid.org/0000-0003-4096-6881 (2026). Carbon footprint (Scope 2) and energy intensity per activity in intermediate-complexity hospitals in the Community of Madrid : panel analysis (2016-2024). "Buildings", v. 16 (n. 7); p. 1381. ISSN 0007-3725. https://doi.org/10.3390/buildings16071381.

Descripción

Título: Carbon footprint (Scope 2) and energy intensity per activity in intermediate-complexity hospitals in the Community of Madrid : panel analysis (2016-2024)
Autor/es:
Tipo de Documento: Artículo
Título de Revista/Publicación: Buildings
Fecha: 1 Abril 2026
ISSN: 0007-3725
Volumen: 16
Número: 7
Materias:
ODS:
Palabras Clave Informales: Hospitales (edificios) ; Edificios para hospitales ; Hospitales de nivel intermedio ; HVAC ; Consumo eléctrico ; Emisiones de CO2 ; Huella de carbono ; Alcance 2 ; Comunidad de Madrid
Escuela: E.T.S. de Edificación (UPM)
Departamento: Construcciones Arquitectónicas y su Control
Licencias Creative Commons: Reconocimiento - Sin obra derivada - No comercial

Texto completo

[thumbnail of 10487741.pdf] PDF (Portable Document Format) - Se necesita un visor de ficheros PDF, como GSview, Xpdf o Adobe Acrobat Reader
Descargar (1MB)

Resumen

Hospital buildings account for 60-80% of healthcare sector electricity consumption, yet robust causal evidence on the relationship between building energy efficiency and emissions per unit of clinical activity remains scarce. This study applies within-group fixed effects estimation to an unbalanced panel of 12 intermediate-complexity hospitals in Madrid, Spain (2016-2024; N = 107 hospital-year observations), controlling for activity volume and exogenous shocks. Cluster-robust standard errors and Wild Cluster Bootstrap inference address the limited number of cross-sectional units (N = 12). We propose a methodological correction for the artificial 74.6% discontinuity in Spain's electricity emission factor (2020-2021) caused by regulatory change. The within-hospital building energy use intensity (EUIe) coefficient is beta = 0.646 (p < 0.001), remarkably stable across six robustness specifications (range: 0.599-0.648; 8.2% variation). Wild Cluster Bootstrap confirms statistical significance despite 75% larger standard errors. A 20 kWh/m(2)& centerdot;year EUIe reduction achievable through Heating, Ventilation and Air Conditioning (HVAC) retrofit in 1980s-era buildings translates into 13 kWh/stay savings, equivalent to 216 tCO(2)/year for median-sized facilities (8.2% reduction). Within R-2 exceeds 0.97 across all specifications. Building envelope and HVAC retrofit constitute the dominant structural intervention for hospital Scope 2 emissions reduction. Facilities with EUIe > 150 kWh/m(2)& centerdot;year should be prioritized for energy efficiency interventions using NextGenerationEU funds.

Más información

ID de Registro: 95780
Identificador DC: https://oa.upm.es/95780/
Identificador OAI: oai:oa.upm.es:95780
URL Portal Científico: https://portalcientifico.upm.es/es/ipublic/item/10487741
Identificador DOI: 10.3390/buildings16071381
URL Oficial: https://www.mdpi.com/2075-5309/16/7/1381
Depositado por: Portal Científico UPM
Depositado el: 28 Abr 2026 17:15
Ultima Modificación: 28 Abr 2026 17:15