Carbon footprint (Scope 2) and energy intensity per activity in intermediate-complexity hospitals in the Community of Madrid : panel analysis (2016-2024).
"Buildings", v. 16
(n. 7);
p. 1381.
ISSN 0007-3725.
https://doi.org/10.3390/buildings16071381.
| Título: | Carbon footprint (Scope 2) and energy intensity per activity in intermediate-complexity hospitals in the Community of Madrid : panel analysis (2016-2024) |
|---|---|
| Autor/es: |
|
| Tipo de Documento: | Artículo |
| Título de Revista/Publicación: | Buildings |
| Fecha: | 1 Abril 2026 |
| ISSN: | 0007-3725 |
| Volumen: | 16 |
| Número: | 7 |
| Materias: | |
| ODS: | |
| Palabras Clave Informales: | Hospitales (edificios) ; Edificios para hospitales ; Hospitales de nivel intermedio ; HVAC ; Consumo eléctrico ; Emisiones de CO2 ; Huella de carbono ; Alcance 2 ; Comunidad de Madrid |
| Escuela: | E.T.S. de Edificación (UPM) |
| Departamento: | Construcciones Arquitectónicas y su Control |
| Licencias Creative Commons: | Reconocimiento - Sin obra derivada - No comercial |
|
PDF (Portable Document Format)
- Se necesita un visor de ficheros PDF, como GSview, Xpdf o Adobe Acrobat Reader
Descargar (1MB) |
Hospital buildings account for 60-80% of healthcare sector electricity consumption, yet robust causal evidence on the relationship between building energy efficiency and emissions per unit of clinical activity remains scarce. This study applies within-group fixed effects estimation to an unbalanced panel of 12 intermediate-complexity hospitals in Madrid, Spain (2016-2024; N = 107 hospital-year observations), controlling for activity volume and exogenous shocks. Cluster-robust standard errors and Wild Cluster Bootstrap inference address the limited number of cross-sectional units (N = 12). We propose a methodological correction for the artificial 74.6% discontinuity in Spain's electricity emission factor (2020-2021) caused by regulatory change. The within-hospital building energy use intensity (EUIe) coefficient is beta = 0.646 (p < 0.001), remarkably stable across six robustness specifications (range: 0.599-0.648; 8.2% variation). Wild Cluster Bootstrap confirms statistical significance despite 75% larger standard errors. A 20 kWh/m(2)& centerdot;year EUIe reduction achievable through Heating, Ventilation and Air Conditioning (HVAC) retrofit in 1980s-era buildings translates into 13 kWh/stay savings, equivalent to 216 tCO(2)/year for median-sized facilities (8.2% reduction). Within R-2 exceeds 0.97 across all specifications. Building envelope and HVAC retrofit constitute the dominant structural intervention for hospital Scope 2 emissions reduction. Facilities with EUIe > 150 kWh/m(2)& centerdot;year should be prioritized for energy efficiency interventions using NextGenerationEU funds.
| ID de Registro: | 95780 |
|---|---|
| Identificador DC: | https://oa.upm.es/95780/ |
| Identificador OAI: | oai:oa.upm.es:95780 |
| URL Portal Científico: | https://portalcientifico.upm.es/es/ipublic/item/10487741 |
| Identificador DOI: | 10.3390/buildings16071381 |
| URL Oficial: | https://www.mdpi.com/2075-5309/16/7/1381 |
| Depositado por: | Portal Científico UPM |
| Depositado el: | 28 Abr 2026 17:15 |
| Ultima Modificación: | 28 Abr 2026 17:15 |
Publicar en el Archivo Digital desde el Portal Científico